Descriere

Certificari:
cULus
EAC
RCM
Conformitate:
IEC/EN 60947-1
IEC/EN 60947-6-1
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL508
CSA C22.2 n°14

Product designation Automatic transfer switch controller for 2 power sources, three phase control, with LCD
display, 110…240VAC supply
Product type designation ATL600
General characteristics
Number of controlled power sources Nr. 2
Display Backlit LCD graphic display 128×80 pixel
Languages Nr. 5
Expandability No
AC Power supply
Rated supply voltage AC VAC 110…240
Operating supply voltage range AC VAC 90…264
Rated frequency Hz 50/60
Operating frequency range Hz 45…66
Immunity time for microbreakings
110VAC ms ≤50
220VAC ms ≤250
Power consumption AC (Max) VA 9.5
Voltage inputs
Maximum rated voltage Ue 100…480VAC L-L (277VAC L-N)
Measurement range V 50…576VAC L-L (333VAC L-N)
Frequency range Hz 45…65
Measurement method True root mean square (TRMS)
Input impedance
phase-phase kΩ >1.0MΩ
phase-neutral kΩ >0.5MΩ
Measuring accurancy ±0.25% f.s. ±1 digit
Wiring mode Single-phase, two-phase, three-phase line with or without neutral and balanced three-
phase system
Digital inputs
Number of digital input Nr. 6
Type of digital input Negative
Digital current inputs mA <8 Low input signal VDC ≤2.2 High input signal VDC ≥3.4 Input signal delay ms ≥50 Relay outputs Number of relay output Nr. 7 Contact arrangement 6 x 1NO-SPST + 1 x C/O-SPDT Electrical life cycles 105 Mechanical life cycles 107 Interface Front optical USB communication port Yes, with CX01 USB dongle (optional) Front optical Wi-Fi communication port Yes, with CX02 Wi-Fi dongle (optional) Functions Programmable source type Single-phase, two-phase, three-phase with or without neutral User alarms Yes Limits Yes Event logging 100 Ambient conditions Temperature Operating temperature min °C -30 max °C +70 Storage temperature min °C -30 max °C +80 Relative humidity % <80% Maximum Pollution degree 2 Overvoltage category 3 Measurement category III Climatic sequence Z/ABDM (IEC/EN 60068-2-61) Shock resistance 15g (IEC/EN 60068-2-27) Vibration resistance 0.7g (IEC/EN 60068-2-6) Housing Execution Flush mount Material Polycarbonate Mounting Flush mount - panel cut-out 138x138 mm Degree of protection IP40 on front, IP65 with optional gasket code EXP8001, IP20 on terminals Dimensions (W x H x D) mm 144 x 144 x 52.2mm Weight g 600 ETIM classification ETIM 8.0 EC000236 - PLC CPU-module

Reviews (0)